Article

An Algorithm for Estimation of SF6 Leakage on Power Substation Assets

by
Ferley Castro Aranda
1,
Rodolfo García Sierra
2,
Andrés Felipe Cerón Piamba
1,
Benjamin Mailhé
3 and
Luis Miguel León Gil
3,*
1
Grupo de Investigación en Alta Tensión-GRALTA, Escuela de Ingeniería Eléctrica y Electrónica, Universidad del Valle, Valle del Cauca, Cali 760032, Colombia
2
Enel Codensa, Bogotá 110221, Colombia
3
Ingeniería Creativa-ICREA, Bogotá 111311, Colombia
*
Author to whom correspondence should be addressed.
Algorithms 2022, 15(2), 38; https://doi.org/10.3390/a15020038
Submission received: 6 December 2021 / Revised: 16 January 2022 / Accepted: 21 January 2022 / Published: 26 January 2022
(This article belongs to the Special Issue Algorithms in Planning and Operation of Power Systems)

Abstract

:
This paper presents an algorithm that evaluates the current state of an asset fleet containing sulphur hexafluoride (SF6) and estimates its leakage in future electrical power substation projects. The algorithm uses simple models and easy tools to facilitate decision making for transmission and distribution system operator companies. The algorithm is evaluated using data provided by ENEL-CODENSA. The corresponding results are shown, and the estimation values obtained are compared with leakage records in existing assets which helps to understand the advantages and limitations of the algorithm.

1. Introduction

In the last two decades, environmental regulations and protocols signed by a great part of the international community, such as the United Nation’s Kyoto [1] and Paris agreements [2], led Distribution System Operators (DSOs) and Transmission System Operators (TSOs) to contribute to reducing their carbon footprint [3]. Some power industry companies have already started to estimate their environmental impact in order to include environmental risk assessment as a strategic objective [4]. A way to mitigate those risks, minimize costs, and maximize performance is to implement an asset management system [5], taking into account that an adequate process to estimate environmental impact is needed.
Sulfur hexafluoride (SF6) has outstanding dielectric properties, with about 2.5 times the dielectric strength of air under the same conditions. SF6 has a low dissociation temperature and high dissociation energy, which makes it an excellent arc quenching gas. Those characteristics led switchgear manufacturers to use it to design their equipment [6]. However, according to EU regulations, SF6 has a global warming potential (GWP) that is 22,800 times greater than that of carbon dioxide (CO2) [7]. It also has a lifetime in the atmosphere of 3200 years relative to CO2 [8]. Aware of this environmental impact, The European Union (EU) is reviewing its fluorinated greenhouse gases regulation, which include SF6, in order to reduce its emissions by two-thirds compared to 2014 levels by 2030 [9]. The EU goal is to be climate-neutral by 2050 [10], which is why the European Network of Transmission System Operators for Electricity (ENTSO-E) is willing to commit to reducing annual SF6 emissions for the existing fleet below 0.5% of the installed SF6 in 2019. New equipment will tend to be SF6 free or have very low GWP by 2050 [11].
According to [12], only 0.1% of human-made global warming in 2006 was related to SF6 emissions, of which around 10% was due to the electric industry. A study from Réseau de Transport d’Électricité (RTE), the transmission system operator of France, showed that its SF6 releases reached seven tons in 2008. The calculated valuation was EUR 16.8 million, using a penalty value of EUR 100 per ton of CO2 [13]. The same company stated that in 2018 its SF6 emissions were equivalent to 138,400 tons of CO2, representing 13% of total RTE emissions [14].
Potential sources of SF6 emissions appear from leakage in SF6-containing equipment and losses during equipment installation, maintenance, and decommissioning [15]. Studies that estimate SF6 leakage in electrical equipment can be found in the literature. In [16], surveys are used to gather information about top-up operations in SF6 circuit breakers, resulting in lower and upper bound weighted-average leak rates. Another work studied the influence of temperature on SF6 leakage in switchgear, giving a lifetime estimation of the analyzed equipment [17]. In order to support decision-making processes, a mixed approach is necessary using the available information of the current fleet and a proper, yet simple, model to estimate the impact of future projects.
This paper proposes an algorithm to evaluate the current state of power substation assets and to estimate SF6 leakage on forthcoming projects. Its main objective is to facilitate management of assets and the general decision-making process. On one hand, the algorithm employs existing fleet data in order to produce straightforward charts that summarize the current state of SF6-containing assets. On the other hand, it allows setting a group of parameters into a simple model for a quick SF6 leakage projection on future projects.
The structure of this work is composed of three sections. The second section presents the algorithm, including the description of each stage. In the third section, the algorithm is applied to SF6 assets data from ENEL-CODENSA, a DSO in Colombia. In the fourth section, the estimation results from the proposed algorithm and real data are compared.

2. Stages of the Algorithm

The purpose of the algorithm is to provide an understanding of the current state of the fleet and the SF6 leakage based on the existing data, as well as an estimation of the leakage of a future potential project, all visualized in a single Microsoft Excel file. The resulting workbook is a flexible tool for the decision-making process.
Figure 1 shows the flowchart of the proposed algorithm. The details of each stage will be illustrated in this section.

2.1. Information Entry

The information of the existing assets is provided by the workbook user. This stage of the algorithm is strictly descriptive. The workbook includes a spreadsheet to insert the data. The necessary fields to produce the charts are: substation and module id, year of commissioning, SF6 initial mass, rate voltage and weight of injected SF6 mass along with the corresponding dates.

Model for Estimation of SF6 Leakage

The model selection was defined by the available information sources and the level of complexity. In a first approach, field monitoring measurements on the equipment were taken into account. For this, it was assumed that gas pressure or density measurements would be available for the fleet equipment, so gas behavior models such as one based on density [18], Van der Waals, or Beattie-Bridgeman models could be implemented [6,19]. However, those models assume that changes in density and/or pressure are due only to gas leaks in the equipment and require data that may be difficult to obtain. If such a model could be interesting for realtime monitoring, its consolidation over long-time data makes it appropriate not for a quick estimation of historic leakage but for fast projection for future projects.
A second approach taken into consideration was to use the information provided by the manufacturer about the nominal leakage rate of each asset. Again, very particular and organized information would be required, such as hard to find historical data, which should not be a problem for new projects.
Considering the drawbacks of the first two approaches, a simple linear model was chosen, which depends only on easy to obtain information. Although the flexibility of the model decreases for the sake of simplicity, the parameters of the model can be changed according to the needs of the user, so different scenarios can be easily visualized. The model assumes a constant SF6 leakage averaged rate per year, which summarizes the combined effect of all assets in all conditions during the lifetime of the project, as observed in previous leakage analyses [6,16,20]. The general model equation is shown below:
m S F 6 = m 0 · F p · ( t t 0 )
where
  • m S F 6 : leaked SF6 mass in kg;
  • m 0 : initial SF6 mass in the asset in kg;
  • F p : reference leak rate in % kg/year;
  • t: year for which the leak is estimated; and
  • t 0 : year of asset commissioning.
There is an additional parameter named L e o l , used to model end-of-life leakages, which considers the emissions related to the handling of the gas for disposal or recycling [21]. This parameter affects only the estimation for the final year t e n d as shown below:
m S F 6 ( t e n d ) = m 0 · F p · ( t e n d t 0 ) + m 0 · L e o l .
Additionally, economic impact parameters are used to make an estimation of SF6 leakage equivalent cost. The model used is presented:
m C O 2 e q = m S F 6 · G W P S F 6
C A = m C O 2 e q · C O 2 c o s t
where
  • m C O 2 e q : mass of equivalent CO2 in kg;
  • G W P S F 6 : Global Warming Potential of SF6;
  • C A : cost of environmental impact; and
  • C O 2 c o s t : cost of CO2 emission per ton.
The parameters of time and initial mass of the assets depend on the project to be analyzed. All the values used in equations 1 to 3 can be edited by the workbook user. In the next section the algorithm is used with real data and selected parameter values are further explained.

2.2. Data Handling

Once the data of the current fleet were entered and the parameters of the future project were defined, the corresponding charts were generated. This stage of the algorithm automated the data manipulation using a Python script that processed all the data and produced the charts, which interacts with the Microsoft Excel workbook to present the results in a clear and user-friendly way. The interaction between Python and Excel allows the correct generation of the charts regardless of the number of rows or the range of the data.

2.3. Results Layout

The results of the algorithm are presented in three spreadsheets of the workbook.

2.3.1. Basic Information Sheet

This sheet allows setting the parameters of the estimation model and offers an overview of the current status of assets and their distribution. Data for the current asset fleet are grouped by rate voltage and displayed in a pie chart. A scatter plot is also produced with the distribution of the SF6 mass in the current assets, grouped by substation and by voltage level.

2.3.2. Current Fleet SF6 Leakage Report Sheet

This sheet addresses the historical analysis of SF6 leakage in the current fleet. The leakage is determined as the SF6 quantity used in a top-up operation. The first two charts plot the mass of SF6 leakage per year and per substation. The rest of the charts depend on a drop-down list that enables selection of the substation for which leakage by year and by module is plotted.

2.3.3. New Fleet Impact Sheet

With the input of parameters into the basic information sheet and given a SF6 mass, the new fleet impact sheet presents an estimated impact that includes leakage per year, equivalent CO2 and annual cost. In addition, a chart plots the accumulated SF6 leakage in the time span defined with the t 0 and t e n d parameters. A drop-down list enables changing the visualization between SF6 leakage kilograms or equivalent CO2 tons.

3. Results of Algorithm Applied to Real Data

The algorithm was validated using data from the current fleet provided by ENEL-CODENSA, the DSO with the largest coverage in Colombia [22].
In this particular case, the Information Entry stage used the information of 410 SF6-containing assets. Table 1 shows a portion of the provided assets data and exemplifies the structure of information that is entered in the current fleet data section of this stage.
Table 2 shows an example of parameters that can be used in the model for the estimation section of the algorithm’s first stage in order to estimate SF6 leakage. However, users may choose different values according to their needs.
The m 0 parameter was arbitrarily picked. The reference leak rate, F p , is the most important parameter, as it defines completely the rate of growth of the gas leakage in the proposed model; 0.5% is the maximum relative leakage rate per year permitted for SF6 in closed pressure systems according to IEC 62271-1:2017 standard [23]. The L e o l parameter selected is the best guess according to [21].
The G W P S F 6 parameter is taken from the European regulation No 517/2014 on fluorinated greenhouse gases [7]. However, a different value may be used based on other sources, as it could actually be 23,500 according to [24]. The cost per ton of CO2 needs to be adjusted to carbon markets or internal corporate considerations.
According to the Carbon Pricing Dashboard from The World Bank, in order to meet the goals of the Paris Agreement, for the power sector the carbon prices need to be in the range of USD 24–39/tCO2e by 2020 [25]. EUR 23/t is slightly above that lower bound.
The results of the data handling stage are shown in Table 3, where data is grouped by substation and rate voltage to sum the total SF6 initial and injected mass values.
The charts generated in stage 2 are shown in Figure 2, Figure 3, Figure 4 and Figure 5. Note that said charts correspond not only to the partial data shown in previous tables but to the full 410 assets. Figure 2 and Figure 3 show the generated charts with the distribution of SF6 mass as explained in Section 2.3.1. Figure 4 displays SF6 leakage per year and per substation. Figure 5 exhibits the result of process described in Section 2.3.3, with the parameter values shown in Table 2. In Figure 2, Figure 3 and Figure 4, the category labeled as other groups data has lower values to allow the correct visualization of results.

4. Discussion

The algorithm was designed to achieve simplicity and clarity. However, it was evaluated to understand its limitations and discuss future work. Table 4 compares the results of the linear model estimation, given by Equation (1), applied to data of the current fleet against the available reports of SF6 leakage, without considering the end-of-life emissions.
Note that a positive error means that the prediction was above the injected mass. That is an indication of better than expected performance regarding gas leakage in the equipment. Negative errors underestimate the leakage. However, reasons for the high error values can be explained and help understand limitations of the algorithm.
Asset 2082 from substation VE, which has the maximum relative error, is a Crompton Greaves SF6 gas insulated circuit breaker. According to the technical brochure, the equipment has a guaranteed maximum leakage rate of less than 1% per year [26]. The model estimation with a F p parameter value of 1% is 0.4 kg of leaked gas, with a corresponding relative error of −28.6%. This reduction in the prediction error applies to another 31 assets.
Asset 2082 from substation FO is an ABB HPL145/25C1 circuit breaker installed in 1991, with 0.42 kg of SF6 injected in 2013 and 1 kg in 2017. This behavior may indicate an inadequate top-up operation in 2013, which led to higher leaks since then. Another influential aspect is the technology available when the circuit breaker was manufactured, as found in [16] where the largest emissions came from the oldest equipment. It is relevant to consider that 142 out of the 410 assets have over 25 years of service.
In addition to the reasons previously mentioned, other factors can be considered to explain high error values:
  • Leak rate error: for this specific implementation of the algorithm, an average leak rate of 0.5% was used. However, assets with a longer operating time or lower quality may have higher leak rates, while newer higher building quality assets may suffer less leakage. To solve this problem, as was seen with asset 2082 from substation VE, catalog data could be used instead of average leakage rate.
  • Important leaks during the recharging process: the model developed does not take into account leaks that may occur during maintenance of the asset, which can result in a significant mass of gas that is not injected. Manufacturers usually recommend good practices, such as those exposed in [6], for the recharging process to avoid SF6 leakage.
  • Damaged equipment: although the estimation in the algorithm itself is not designed to be compared with historical data, an exaggerated deviation from the model estimation may indicate damages in an asset. Along with the record of top-ups, this kind of result offers the opportunity to anticipate failures and to take proper actions early in order to analyze the situation in more detail and start preventive maintenance.

5. Conclusions

An algorithm for estimation of SF6 leakage in electrical equipment on power substations was proposed. In the first stage, the information is entered into a Microsoft Excel workbook that includes spreadsheets to fill with current fleet data including top-up records and parameters for leakage estimation of a future project. This well-known tool facilitates the entry of information and the visualization of results. In the second stage, a Python script generates charts by interacting with the workbook. With this, the number of rows, missing records, or range of data do not affect the quality of charts. The final stage of the algorithm presents all the results in three different spreadsheets. Various scenarios can be seen by changing the parameters used to estimate the impact of a new fleet.
In the discussion section it became clear that the algorithm results are not to be compared with historical data, since the objective has a more global approach. When such comparison is made, the explanation of obtained results needs a detailed examination of particular assets. The maximum relative errors found in Table 4 were explained by looking at the characteristics of the assets. However, this comparison presents itself as an opportunity for a better and appropriate selection of parameters.
Atypical values, if any, are clearly identified in generated charts from the results layout stage of the algorithm. This layout makes situations that need special review more evident, such as the CI substation SF6 leakage observed in Figure 4. This is the way by which the algorithm helps identify strange behavior instead of the comparison of model estimation to historical data.
In this paper, the simple structure of the algorithm and workbook tool was highlighted, as well as its capacity to globally visualize the state of an asset fleet for further decision making and quick estimation of the environmental impact of future projects.

Author Contributions

Conceptualization and research proposal—direction, F.C.A. and R.G.S.; methodology, F.C.A., A.F.C.P. and B.M.; software, B.M.; validation, F.C.A., R.G.S., A.F.C.P. and B.M.; formal analysis, B.M.; investigation, R.G.S., B.M. and A.F.C.P.; resources, R.G.S., F.C.A.; data curation, B.M., R.G.S.; writing—original draft preparation, B.M. and L.M.L.G.; writing—review and editing, B.M. and L.M.L.G.; visualization, B.M., L.M.L.G.; supervision, F.C.A. and A.F.C.P.; project administration, F.C.A., R.G.S. and A.F.C.P.; funding acquisition, F.C.A. and R.G.S. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by ENEL-CODENSA.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Data is property of ENEL-CODENSA.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. United Nations. Kyoto Protocol—United Nations Framework Convention on Climate Change. 1998. Available online: http://unfccc.int/resource/docs/convkp/kpeng.pdf (accessed on 2 November 2021).
  2. United Nations. Paris Agreement—United Nations Framework Convention on Climate Change. 2015. Available online: http://unfccc.int/files/essential_background/convention/application/pdf/english_paris_agreement.pdf (accessed on 2 November 2021).
  3. Swiss Grid. Decarbonizing the Energy System—The Role of Transmission System Operators. Available online: https://www.swissgrid.ch/dam/swissgrid/about-us/company/sustainability/decarbonisation-role-of-TSOs-en.pdf (accessed on 2 November 2021).
  4. CIGRÉ WG C1.25. Asset Management Decision Making Using Different Risk Assessment Methodologies; CIGRÉ: Paris, France, 2013. [Google Scholar]
  5. Alvarez, D.L.; Rosero, L.S.; Rivera, S.R.; Romero, A.A. A Framework For Asset Management in Electrical Systems, Part I: Conceptual Model. In Proceedings of the 2019 IEEE Workshop on Power Electronics and Power Quality Applications (PEPQA), Manizales, Colombia, 30–31 May 2019. [Google Scholar]
  6. Koch, D. SF6 Properties, and Use in MV and HV Switchgear; Cahier Techniques; Schneider Electric: Grenoble, France, 2003; Volume 188. [Google Scholar]
  7. Schulz, M.; Kourkoulas, D. Regulation (EU) No 517/2014 of The European Parliament and of the council of 16 April 2014 on fluorinated greenhouse gases and repealing Regulation (EC) No 842/2006. Off. J. Eur. Union 2014, 195–230. [Google Scholar]
  8. Intergovernmental Panel on Climate Change (IPCC). Climate Change 2007—The Physical Science Basis: Working Group I Contribution to the Fourth Assessment Report of the IPCC; Cambridge University Press: Cambridge, UK, 2007. [Google Scholar]
  9. DG Climate Action–Unit A2: Climate Finance, Mainstreaming, Montreal Protocol. Proposal for a Regulation on Fluorinated Greenhouse Gases (Recast). 2020. Available online: https://eur-lex.europa.eu/legal-content/ES/ALL/?uri=PI_COM:Ares(2020)3402178 (accessed on 5 November 2021).
  10. European Commission. 2050 Long-Term Strategy. Available online: https://ec.europa.eu/clima/eu-action/climate-strategies-targets/2050-long-term-strategy_en (accessed on 5 November 2021).
  11. ENTSO-E. ENTSO-E Contribution to the EC Roadmap Consultation Concerning the Revision of the Fgas-Regulation. Available online: https://ec.europa.eu/info/law/better-regulation/have-your-say/initiatives/12479-Fluorinated-greenhouse-gases-review-of-EU-rules-2015-20-/F550132_en (accessed on 9 November 2021).
  12. Ficheux, A.; Depres, D.; Laruelle, E.; Kieffel, Y.; Prieur, P. Limiting SF6 Gas Emissions by Optimization of Design and Testing of Gaskets in High Voltage Gas-Insulated Substations; CIGRÉ Paper C3-209; CIGRÉ: France, Paris, 2012. [Google Scholar]
  13. Serres, E.; Martin, G.D.S.; Isoard, J. External Costs of Transmission: State of RTE’s Knowledge and Practical Experience; CIGRÉ: France, Paris, 2010. [Google Scholar]
  14. RTE. Bilan des Émissions de Gaz à Effet de Serre 2018 de RTE. Available online: https://assets.rte-france.com/prod/public/2020-09/Bilan%20gaz%20effet%20de%20serre%20RTE%202018.pdf (accessed on 9 November 2021).
  15. EPA. Overview of SF6 Emissions Sources and Reduction Options in Electric Power Systems. 2018. Available online: https://www.epa.gov/sites/default/files/2018-08/documents/12183_sf6_partnership_overview_v20_release_508.pdf (accessed on 11 November 2021).
  16. Blackman, J.; Averyt, M.; Taylor, Z. SF6 leak rates from high voltage circuit breakers-US EPA investigates potential greenhouse gas emissions source. In Proceedings of the 2006 IEEE Power Engineering Society General Meeting, Montreal, QC, Canada, 18–22 June 2006. [Google Scholar]
  17. Tits, Y.; Delouvroy, G.; Marginet, J.; Francois, A.; Van Den Berg, M. Life time estimation of SF6 MV Switchgear according to on-site conditions in DNO’s distribution networks. In Proceedings of the 21st International Conference on Electricity Distribution (CIRED), Frankfurt, Germany, 6–9 June 2011. [Google Scholar]
  18. CIGRÉ WG B3.25. SF6 Analysis for AIS, GIS and MTS Condition Assessment; CIGRÉ: France, Paris, 2014. [Google Scholar]
  19. Green, D.W.; Perry, R.H. Perry’s Chemical Engineers’ Handbook; McGraw-Hill Education: New York, NY, USA, 2008. [Google Scholar]
  20. Fuhai, L.; Zhan, T.; Yeyuan, L.; Yongqiang, D. Analysis of the Causes of Gas Leakage of a 500 kV SF6 Circuit Breaker. In IOP Conference Series: Earth and Environmental Science; IOP Publishing: Bristol, UK, 2019; Volume 310. [Google Scholar]
  21. Heckmann, W.; Reimann, T. Impact Assessment of F-Gas Free Medium Voltage Switchgear—Modeling Scenarios of MV Switchgear Installation Development and Impact on SF6 Emissions; Fraunhofer IEE: Kassel, Germany, 2020. [Google Scholar]
  22. About ENEL-CODENSA. Available online: https://www.enel.com.co/en/about-enel/enel-codensa.html (accessed on 17 November 2021).
  23. IEC 62271-1: 2017. High-Voltage Switchgear and Controlgear-Part 1: Common Specifications for Alternating Current Switchgear and Controlgear; International Electrotechnical Commission: London, UK, 2017. [Google Scholar]
  24. Myhre, G.; Shindell, D.; Bréon, F.; Collins, W.; Fuglestvedt, J.; Jianping, H.; Koch, D.; Lamarque, J.; David, L.; Mendoza, B.; et al. Anthropogenic and Natural Radiative Forcing; Cambridge University Press: Cambridge, UK, 2013. [Google Scholar]
  25. The World Bank. Carbon Pricing Dashboard—What Is Carbon Pricing. Available online: https://carbonpricingdashboard.worldbank.org/what-carbon-pricing (accessed on 13 January 2022).
  26. Crompton Greaves Ltd. Guaranteed Technical Particulars. Available online: https://www.tstransco.in/it_uploads/Drawings_GTPs_CB_CGL.pdf (accessed on 13 January 2022).
Figure 1. Flowchart of the algorithm.
Figure 1. Flowchart of the algorithm.
Algorithms 15 00038 g001
Figure 2. Distribution of SF6 mass based on ENEL-CODENSA assets data.
Figure 2. Distribution of SF6 mass based on ENEL-CODENSA assets data.
Algorithms 15 00038 g002
Figure 3. Distribution of SF6 mass based on ENEL-CODENSA assets data.
Figure 3. Distribution of SF6 mass based on ENEL-CODENSA assets data.
Algorithms 15 00038 g003
Figure 4. Historical analysis of SF6 top-ups in ENEL-CODENSA assets.
Figure 4. Historical analysis of SF6 top-ups in ENEL-CODENSA assets.
Algorithms 15 00038 g004
Figure 5. Estimation of SF6 leakage for a new project according to the parameters given in Table 2.
Figure 5. Estimation of SF6 leakage for a new project according to the parameters given in Table 2.
Algorithms 15 00038 g005
Table 1. Current fleet data example.
Table 1. Current fleet data example.
SubstationIDYear of Comm.Rate Voltage [kV]SF6 Initial Mass [kg]SF6 Injected Mass [kg]Injection Date
VE201220081158NANA
VE203220081158NANA
VE204220061158NANA
VE206220081158NANA
VE207219861154NANA
VE2082200811580.5630 August 2012
VE2092200811512NANA
VE2102200811512NANA
Table 2. Parameters used for the estimation of SF6 leakage in a new project.
Table 2. Parameters used for the estimation of SF6 leakage in a new project.
ParameterValue
m 0 10 kg
F p 0.5% kg/year
t e n d 35 years
L e o l 10%
G W P S F 6 22,800
C O 2 c o s t 23 EUR/t
Table 3. Data handling stage results example.
Table 3. Data handling stage results example.
SubstationRate Voltage [kV]Total SF6 Initial Mass [kg]Total SF6 Injected Mass [kg]
VE115680.56
Table 4. Comparison of model results against historical data.
Table 4. Comparison of model results against historical data.
SubstationIDSF6 Injected [kg]Model Prediction [kg]Relative Error %
FO20821.420.65−54.23
UM20620.40.18−55.00
FO20421.050.725−30.95
MU20120.550.324−41.09
AU20520.950.6−36.84
TU30622.061.68−18.45
UM20320.80.66−17.50
VE20820.560.2−64.29
LG20320.70.68−2.86
TZ20120.880.8−9.09
NO31220.80.9518.75
AJ20120.50.6836.00
CO20420.320.16−50.00
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Castro Aranda, F.; García Sierra, R.; Cerón Piamba, A.F.; Mailhé, B.; Gil, L.M.L. An Algorithm for Estimation of SF6 Leakage on Power Substation Assets. Algorithms 2022, 15, 38. https://doi.org/10.3390/a15020038

AMA Style

Castro Aranda F, García Sierra R, Cerón Piamba AF, Mailhé B, Gil LML. An Algorithm for Estimation of SF6 Leakage on Power Substation Assets. Algorithms. 2022; 15(2):38. https://doi.org/10.3390/a15020038

Chicago/Turabian Style

Castro Aranda, Ferley, Rodolfo García Sierra, Andrés Felipe Cerón Piamba, Benjamin Mailhé, and Luis Miguel León Gil. 2022. "An Algorithm for Estimation of SF6 Leakage on Power Substation Assets" Algorithms 15, no. 2: 38. https://doi.org/10.3390/a15020038

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop