Article

Temperature Fluctuation Attenuation of Circulating Cooling Water Using Dynamic Thermal Filtering

Center of Ultra-precision Optoelectronic Instrument, Harbin Institute of Technology, Harbin 150080, China
*
Author to whom correspondence should be addressed.
Appl. Sci. 2020, 10(15), 5338; https://doi.org/10.3390/app10155338
Submission received: 17 June 2020 / Revised: 19 July 2020 / Accepted: 30 July 2020 / Published: 2 August 2020
(This article belongs to the Section Mechanical Engineering)

Abstract

:
The Demand for circulating cooling water (CCW) with high temperature stability and a quick response to temperature control is essential for precision engineering, so a dynamic thermal filtering method is proposed in this paper. Some CCW is bypassed, blocked, and used as a thermal capacity medium, and the temperature fluctuation of CCW is significantly reduced by heat exchanging with the medium. The temperature of the medium dynamically follows the set value of the CCW temperature by real time updating, and so realizes a quick CCW temperature control response. The attenuation ratio of temperature fluctuation was derived, theoretically validating the effectiveness of the method. The experimental results indicate that a CCW temperature fluctuation attenuation ratio of tens of dB (−3.47 dB, −6.91 dB, −10.97 dB and −15.28 dB corresponding to temperature fluctuation frequencies of 0.01 Hz, 0.025 Hz, 0.053 Hz and 0.105 Hz, respectively) is achieved by the proposed method. The updating time of thermal capacity medium is 82 s, which means that the temperature fluctuation attenuation remains functionally valid when the set value of CCW changes. The proposed method is low cost in operation and provides an effective approach to satisfy the challenging demand for CCW with high stability and a good dynamic temperature control performance.

1. Introduction

In the fields of precision manufacturing, more than 40–70% of machining errors result from thermal deformation of machine tools and work pieces [1], while circulating water cooling is a key technology against thermal pollution. Circulating cooling water (CCW) is usually used for temperature maintenance of motors, drivers, and other power devices. Therefore, the requirement for CCW with high temperature stability and quick response of temperature control is found in the fields of lithography, optical machining, and so on [2,3,4,5].
Lithography, for instance, has a requirement for overlay accuracy of up to 1.4 nm, while the technical node of the advanced stepping and scanning lithography machine is below 45 nm. However, the peak power of the thermal pollution produced by motors, drivers, laser sources, and various electrical circuits reaches up to several kilowatts. Thus, CCW with a temperature stability of ±0.01 K is used as a direct cooling medium to maintain the temperature stability of the objective lens within ±0.01 K, and also as a temperature reference medium to produce an “air shower” for temperature stability of up to 2.3 mK/5 min, to maintain the air refractive index for the ultra-precision laser interferometry [3,5]. Besides, it is preferred that the temperature of CCW is able to vary quickly along with the pre-set power curve of motors, rather than conventional motor cooling with CCW of constant temperature. In the applications of the electrical spindle cooling of optical machining [6,7,8], a CCW temperature control response time of tens of seconds of is also demanded, to achieve “servo” thermal management according to the variation of the spindle rotating speed. For example, in 2015, Weiguo Gao used two CCW machines to provide two streams of CCW with different temperatures, then mixed the two streams to produce the CCW for spindle thermal control. As a result, the temperature of mixed CCW can be regulated quickly by modifying the mixing percentage [6]. Therefore, precision manufacturing is marching forward to an “atom era”; accordingly, CCW temperature control with high stability and good dynamic performance becomes a challenging task to be solved.
Conventionally, in order to improve the temperature stability of CCW, thermal inertia of CCW is enlarged by introducing a water tank into the temperature control system of CCW. As a result, a quick temperature control response can hardly be achieved due to the enlarged distributive delay which comes from the introduced thermal inertia [9,10,11,12,13], i.e., the dynamic performance is sacrificed for higher temperature stability. Lawton K.M. et al. presented temperature fluctuation attenuators based on the principle of introducing additional thermal capacity medium. In 2001, Lawton used water, which is sealed in one chamber of a heat exchanger, as thermal capacity medium. Then, CCW flows through another chamber of the heat exchanger, thus the temperature fluctuation of CCW is reduced by the large thermal capacity of the sealed water [14]. In 2003, Lawton used stainless-steel balls as thermal capacity material, with CCW flowing through the balls, thus the temperature fluctuation of CCW is reduced by the large thermal capacity of the stainless-steel balls [15]. Materials with large thermal capacity, including stainless-steel balls and water, are introduced as the medium, and the temperature fluctuation of water is smoothed by heat exchanging with the medium. This method provides a new approach to the high attenuation ratio of water temperature fluctuation. However, the attenuators only function around a fixed temperature point. Once the set value of the CCW temperature is changed, the attenuator is functionally invalid, and becomes a thermal interference source, which means that the method is only applicable for water cooling applications that demand CCW of constant temperature. Temperature fluctuation attenuators using phase change material (PCM) as thermal capacity medium [16,17,18,19,20] are also proposed and attract much attention. PCM has large latent thermal capacity at its phase change temperature point, and can absorb or release great thermal energy during the process of phase change. In 2004, Esam M. Alawadhi presented a numerical study to evaluate the temperature fluctuation attenuation of water based on PCM, which indicated that lower flow rate of water and larger quantity of PCM could improve the performance of temperature fluctuation attenuation [18]. In 2014, Pavel Charvat presented the experimental investigation to validate the stabilization of the flowing water temperature with PCM, and a kind of paraffin-based PCM is used to cover a tube as thermal capacity medium. As a result, more than 90% of temperature fluctuation of the water flowing through the tube is reduced [16,17]. A variety of PCMs with different phase change temperature points have been investigated and used to form attenuators. However, a PCM has a fixed phase change temperature point. Therefore, one PCM based attenuator can only reduce the temperature fluctuation around the fixed temperature point of the employed PCM. Besides, new materials like nanofluids have are also attracting attention, since the enhanced conventional heat transfer performance can improve the temperature fluctuation attenuation [21,22].
Therefore, previous work mostly concentrates on the realization of high temperature stability of CCW, while the dynamic performance of temperature control is rarely paid attention to. Therefore, a dynamic thermal filtering method (DTFM) is proposed in this paper. Some of the CCW is blocked and used as thermal capacity medium to filter the temperature fluctuation of CCW. The medium can be real time updated to dynamically follow the set value of CCW temperature, thus to achieve the quick response of CCW temperature control. The proposed method is theoretically and experimentally validated.

2. Principle

The basic concept of the proposed DTFM is shown in Figure 1. The DTFM attenuator consists of a heat exchanger, two servo valves, two precision temperature sensors, and a control module. The control module is used to implement on/off control of the servo valves according to the feedback of the temperature sensors. The attenuator is cascaded together with a CCW machine and a thermal load to compose an enhanced CCW temperature control system.
The high temperature stability of CCW is achieved by thermal filtering. As shown in Figure 1, some CCW is bypassed and blocked in one chamber of the heat exchanger, serving as thermal capacity medium. Temperature fluctuation of CCW, which flows through the other chamber of the heat exchanger, is attenuated by the heat exchanging with the medium. Therefore, the temperature stability of the CCW is significantly improved through thermal filtering effect.
The quick response of CCW temperature control is achieved by making the temperature of thermal capacity medium dynamically follow the set value of CCW temperature through the real time updating of the medium. When the temperature set value of the CCW machine changes, temperature sensor A detects the change, then provides feedback signal to the control module. Then the control module switches on servo valve 1 and switched off servo valve 2 to make CCW flow into the thermal capacity medium chamber to update the medium. Meanwhile, the temperature of the outflow from the medium chamber is monitored by temperature sensor B. When the temperature at point B equals to the temperature at point A, which means that the water in the medium chamber is totally updated, the servo valve 1 is switched off and the servo valve 2 is switched on. In this way, the change of temperature set value of CCW is dynamically followed.
The updating time of the thermal capacity medium Tmed can be given by
T med = V med F med
where Vmed is the volume of the thermal capacity medium chamber, and Fmed is the volume flow rate of CCW.
Before that the DTFM attenuator is introduced into the enhanced CCW system, the response time of CCW temperature control is determined by the dynamic performance of the temperature closed loop control of the CCW machine. In general, the response time of the temperature control of a CCW machine used in precision manufacturing ranges from tens of second to several minutes. After the DTFM attenuator is cascaded into the system, the response time of the temperature control of the system Tsys can be expressed as
T sys = max ( T mac , T med )
where Tmac is the response time of temperature control of the CCW machine, and Tmed is the updating time of thermal capacity medium. Therefore, a design criterion of DTFM attenuator can be expressed as follows:
T mac T med
If the criterion is satisfied, the quick response of CCW temperature control is not degraded.

3. Modeling

The DTFM attenuator is designed using a tube-tank heat exchanger for its high heat exchanging efficiency with compact structure. The structure of the tube-tank heat exchanger is shown in Figure 2. It consists of a square tank and an array of parallel tubes evenly arranged in the tank. The volume of the tank is divided into two chambers. One chamber is between the tubes and the wall of the tank, serving as the thermal capacity medium chamber. The other chamber is given by the inner volume of all tubes, serving as the CCW chamber. So CCW flows through the tubes, and the tubes are evenly immersed in the thermal capacity medium. A distributor is set in the upper part of the heat exchanger to guide CCW to flow into the tube array. A collector is set in the lower part of the heat exchanger to converge CCW from the tube array. The effect of temperature fluctuation attenuation is mainly contributed by the tube array, and partly contributed by the upper distributer and lower collector.
The designed tube-tank heat exchanger is composed of 36 tubes and a stainless-steel tank. The length of each tube Ltube is 0.7 m, the diameter of each tube Rtube is 8 mm, and the center spacing between two neighboring tubes d is 32 mm. The height of the tank L is 0.7 m, and the width b is 0.23 m. The total flow rate of CCW Fm is 16 L/min.
CCW flows into the upper distributor from the inlet header, and then flows through all tubes with same flow rate. Since the tubes are evenly immersed in the thermal capacity medium, spatial structural symmetry results in the same thermal characteristics of all tubes. The flow rate is kept small enough to make the laminar flow dominant in the tubes. Therefore, only convective heat transfer is considered to calculate the temperature fluctuation attenuation of the tube array, while the effect of mixing in the tubes is ignored. On the other hand, in the lower collector, sub-streams from the tubes act as jets and converge together, thus water mixing rather than heat transfer is the main effect contributing to CCW temperature averaging. The tank is covered with thermal isolation material to avoid heat exchange with ambient air.
The temperature fluctuation attenuation of the DTFM attenuator is mathematically modeled by using transfer function method with reference to [14]. Transfer functions of the distributor, the tube-tank part, and the collector are defined as the fluctuation ratios of output temperature to input temperature of CCW. The total temperature fluctuation attenuation ratio of the DTFM attenuator is the product of transfer functions of all the three parts.
The transfer functions of the distributor, tube-tank part and collector are expressed as follows:
r dis ( f ) = exp ( u a u a 2 + 4 ( λ / ρ c w ) 2 j π f C a 2 λ / ρ c w L d )
r cel ( f ) = 1 1 + ( ρ V acc / F m ) 2 j π f
r att ( f ) = exp ( 1 f m c w R Re ( 2 j π f R C a 2 j π f R C a + 1 ) )
where ρ is the density of water, Vdis is the volume of distributor, Fm is the total volume flow rate of CCW, fm is the volume flow rate of each tube, ua is the average water velocity in the collector, λ is thermal conductivity of water, Ca is the thermal capacity of a single tube, La and Ld are the height of collector and distributor respectively, cw is the specific thermal capacity of water, and R is the thermal resistance of the heat exchanger. The CCW temperature fluctuation is defined as the maxima of peak-to-peak value of temperature oscillations of CCW temperature.
The total temperature fluctuation attenuation ratio of the DTFM attenuator is
r ( f ) = r dis ( f ) r cel ( f ) r att ( f )
According to Equation (1), the updating time of the thermal capacity medium Tmed is
T med = ( b 2 L N L π ( R tube / 2 ) 2 ) ρ F m = 82   s
The response time of temperature control of the CCW machine used in this paper is ~200 s, so the design criterion of the DTFM attenuator given by Equation (3) is well satisfied, and the dynamic performance of the CCW temperature control is guaranteed. On the other hand, the band of closed loop temperature control of the CCW machine is from 0 to 0.005 Hz, which means that the CCW temperature fluctuation below 0.005 Hz due to power fluctuation of the thermal load or other thermal interference can be well reduced by closed loop temperature control of the CCW machine. However, the temperature fluctuation above 0.005 Hz is beyond the capability of the CCW machine, which is intended to be attenuated by the DTFM attenuator.
The theoretical temperature fluctuation attenuation ratio of the DTFM attenuator is shown in Figure 3. The temperature fluctuation attenuation ratio above 0.01 Hz is better than −10 dB. In addition, the higher the frequency of CCW temperature fluctuation is, the better the attenuation ratio will be. Therefore, the temperature stability performance is effectively enhanced while the dynamic response is kept, when the DTFM attenuator is introduced into the system. The challenging demand for the precision and dynamic temperature control of CCW in precision manufacturing is well met.

4. Experiment and Discussion

4.1. Experimental Setup

The effectiveness of the proposed DTFM method is experimentally verified. The schematic diagram and photo of the experimental setup are shown in Figure 4 and Figure 5 respectively.
Two CCW machines (STTP5000-1/10 of SMEE) are used to produce the streams of CCW with different temperatures. Each CCW machine is capable of supplying CCW with a maximum flow rate of 55 L/min and temperature stability of ±0.01 °C. The two streams of CCW are alternately pumped into the DTFM attenuator through the control of a pair of electromagnetic three-way valves. In this way, a stream of CCW with square temperature waveform is produced, serving as the standard test signal for the DTFM attenuator. The amplitude of the square waveform depends on the difference in temperature of the two CCW streams from the two CCW machines, and the frequency of the square waveform depends on the switching frequency of the three-way valves.
Two temperature sensors (5641 of Fluke) with an accuracy of ±0.001 °C are used to monitor the temperature at point A and B of the DTFM attenuator. A flowmeter (FD-Q10C of Keyence) with the repeatability of ±0.5% in the full measuring range of 0–40 L/min is used to measure the CCW flow rate. A control module (homemade with STM32F407 as CPU) is used for valve control and data acquisition. A PC is used as the human machine interface.

4.2. Results and Discussion

The temperature fluctuation attenuation ratio of the DTFM attenuator is tested. Additionally, the temperature set values of the two CCW machines are 22.5 °C and 21.5 °C respectively. In actual CCW temperature control systems, the frequency of CCW temperature fluctuation is hardly over 0.1 Hz. Moreover, the CCW temperature fluctuation of frequency lower than 0.005 Hz can be directly eliminated by the temperature closed loop feedback control of the CCW temperature control system. Therefore, the switching frequencies of the two three-way valves are defined as 0.01 Hz, 0.02 Hz, and 0.05 Hz for three experiment times.
It is hoped that a CCW stream with ideal square temperature waveform could be obtained. However, because of the thermal inertia between the outer header of the CCW machines and the inlet header of the DTFM attenuator, including thermal inertia of pipes, valves, and so on, the temperature waveform at inlet header of the DTFM attenuator is smoothed and distorted, as shown in Figure 6.
Therefore, the frequency analysis of CCW temperature waveforms is carried out to illustrate the performance of fluctuation attenuation in frequency domain, as shown in Figure 7. The main frequencies of distorted CCW temperature waveforms at inlet header of the DTFM attenuator are 0.01 Hz, 0.025 Hz, and 0.053 Hz, respectively, while the corresponding temperature fluctuation attenuation ratios are −3.47 dB, −6.19 dB, and −10.97 dB, respectively. The temperature fluctuation attenuation ratio corresponding to 0.105 Hz is −15.28 dB.
The comparison of experimental results with theoretical modeling results is shown in Figure 8. It can be seen that the values of experimental results are ~5 dB worse than the theoretical results. There are many factors which may result in the difference between experimental and theoretical values, such as indispensable approximation in the transfer functions, thermal dissipation of the experimental set up and so on. Therefore, the difference of ~5 dB is acceptable in this work, since the trend of the experimental results agrees well with the theoretical results.
Conventional temperature fluctuation attenuation methods can provide a super large attenuating ratio, such as more than −60 [email protected] Hz presented by Lawton, K.M. [14], however, the thermal capacity medium in previous work are all non-updatable, which means that the temperature fluctuation attenuation is available around a fixed temperature. Thus, the conventional methods can not satisfy the demand of temperature fluctuation attenuation in dynamic temperature control system, since the dynamic performance of the system is sacrificed for better temperature stability by the introduced thermal inertia. Compared with conventional methods, the proposed DTFM can be applied for the applications demanding dynamic temperature control of CCW.

5. Conclusions

This paper proposes a dynamic thermal filtering method, which can significantly reduce the temperature fluctuation of CCW and achieve the quick response of CCW temperature control. A DTFM based attenuator is achieved with a tube-tank heat exchanger. Theoretical analysis has been carried out with the designed attenuator, and the performance of the attenuator is verified by experiments. In summary, conclusions are as follows:
  • Theoretical results indicate that the attenuator based on DTFM has low-pass characteristics for temperature fluctuation. Though there is only a few of dB beyond 0.005 Hz, the temperature fluctuation can be eliminated by the closed loop feedback control of the temperature control system.
  • The attenuation ratio of tens of dB (−3.47 dB, −6.91 dB, −10.97 dB and −15.28 dB, corresponding to temperature fluctuation frequencies of 0.01 Hz, 0.025 Hz, 0.053 Hz and 0.105 Hz, respectively) is achieved, while the thermal capacity medium updating time is 82 s, which means that the designed DTFM attenuator can remarkably improve the temperature stability of CCW with the response time of CCW temperature control less than one minute.
  • The conventional methods can provide quite large attenuation ratio of temperature fluctuation, but cannot satisfy the demand of temperature fluctuation attenuation from dynamic temperature control system. Compared with the conventional methods, the proposed method can be applied for the applications demanding the dynamic temperature control of CCW, since the updatable thermal capacity medium is introduced.
  • Our further work will focus on the structure optimization of the attenuator to achieve a larger attenuation ratio with more compact size.

Author Contributions

Conceptualization, Y.L., J.C. and J.T.; Funding acquisition, J.C. and J.T.; Investigation Y.L.; Methodology, J.C. and J.T.; Project administration, J.C. and J.T.; Resources, Y.L.; Visualization, X.B. and Y.Z.; Writing—original draft, Y.L.; Writing—review & editing, Y.L., J.C. and J.T. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by National Natural Science Foundation of China, grant number 51675139 and the Fundamental Research Funds for the Central Universities.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Mayr, J.; Jedrzejewski, J.; Uhlmann, E.; Donmez, M.A.; Knapp, W.; Härtig, F.; Wendt, K.; Moriwaki, T.; Shore, P.; Schmitt, R.; et al. Thermal issues in machine tools. CIRP Ann. -Manuf. Technol. 2012, 61, 771–791. [Google Scholar] [CrossRef] [Green Version]
  2. Yamada, A. Arf immersion lithography for 45-nm and beyond. Proc. Spie-Int. Soc. Opt. Eng. 2007, 6607, 66071–66081. [Google Scholar]
  3. Zhao, Y.; Trumper, D.L.; Heilmann, R.K.; Schattenburg, M.L. Optimization and temperature mapping of an ultra-high thermal stability environmental enclosure. Precis. Eng. 2010, 34, 164–170. [Google Scholar] [CrossRef]
  4. Cui, L.Y.; Zhang, D.W.; Gao, W.G.; Qi, X.Y.; Shen, Y. Thermal errors simulation and modeling of motorized spindle. Adv. Mater. Res. 2011, 154–155, 1305–1309. [Google Scholar] [CrossRef]
  5. Tay, A.; Chua, H.T.; Wang, Y.H.; Ngo, Y.S. Equipment design and control of advanced thermal-processing module in lithography. IEEE Trans. Ind. Electron. 2010, 57, 1112–1119. [Google Scholar] [CrossRef]
  6. Liu, T.; Gao, W.; Tian, Y.; Zhang, H.; Chang, W.; Mao, K.; Zhang, D. A differentiated multi-loops bath recirculation system for precision machine tools. Appl. Therm. Eng. 2015, 76, 54–63. [Google Scholar] [CrossRef] [Green Version]
  7. Mayr, J.; Ess, M.; Pavliček, F.; Weikert, S.; Spescha, D.; Knapp, W. Simulation and measurement of environmental influences on machines in frequency domain. CIRP Ann. -Manuf. Technol. 2015, 64, 479–482. [Google Scholar] [CrossRef]
  8. Li, Y.; Zhao, W.; Lan, S.; Ni, J.; Wu, W.; Lu, B. A review on spindle thermal error compensation in machine tools. Int. J. Mach. Tools Manuf. 2015, 95, 20–38. [Google Scholar] [CrossRef]
  9. Manske, E.; Jäger, G.; Hausotte, T.; Füßl, R. Recent developments and challenges of nanopositioning and nanomeasuring technology. Meas. Sci. Technol. 2012, 23, 074001. [Google Scholar] [CrossRef]
  10. Unni, P.K.M.; Gunasekaran, M.K.; Kumar, A. ±30 μk temperature controller from 25 to 103 °C: Study and analysis. Rev. Sci. Instrum. 2003, 74, 231. [Google Scholar] [CrossRef]
  11. Nagata, K.; Okumura, M.; Maio, K.; Fujii, A.; Andoh, H.; Morimura, T.; Hayakawa, H. High-resolution and high-stability electromagnetic-deflection control system for eb lithography system. Emerg. Lithogr. Technol. V 2001, 4343, 692–703. [Google Scholar]
  12. Lawton, K.M.; Patterson, S.R. A high-stability air temperature control system. Precis. Eng. 2000, 24, 174–182. [Google Scholar] [CrossRef]
  13. Hirasawa, S.; Koike, K.; Kawanami, T.; Shirai, K. Effect of error in predictive model of model prediction control to minimize temperature change of plate with varying heat generation. J. Mach. Manuf. Autom. 2013, 2, 71–78. [Google Scholar]
  14. Lawton, K.M.; Patterson, S.R.; Keanini, R.G. Precision temperature control of high-throughput fluid flows: Theoretical and experimental analysis. J. Heat. Transf. 2001, 123, 796–802. [Google Scholar] [CrossRef]
  15. Lawton, K.M.; Patterson, S.R.; Keanini, R.G. Direct contact packed bed thermal gradient attenuators: Theoretical analysis and experimental observations. Rev. Sci. Instrum. 2003, 74, 2886–2893. [Google Scholar] [CrossRef] [Green Version]
  16. Vít, T.; Charvat, P.; Stetina, J.; Pech, O.; Klimes, L.; Ostry, M.; Dančová, P.; Novotný, P. Experimental investigation of stabilization of flowing water temperature with a water-pcm heat exchanger. EPJ Web Conf. 2014, 67, 02046. [Google Scholar]
  17. Charvat, P.; Klimes, L.; Stetina, J.; Ostry, M. Thermal storage as a way to attenuate fluid-temperature fluctuations: Sensible-heat versus latent-heat storage materials. Mater. Tehnol. 2014, 48, 423–427. [Google Scholar]
  18. Alawadhi, E.M. Temperature regulator unit for fluid flow in a channel using phase change material. Appl. Therm. Eng. 2005, 25, 435–449. [Google Scholar] [CrossRef]
  19. Oró, E.; de Gracia, A.; Castell, A.; Farid, M.M.; Cabeza, L.F. Review on phase change materials (PCMS) for cold thermal energy storage applications. Appl. Energy 2012, 99, 513–533. [Google Scholar] [CrossRef]
  20. Klimes, L.; Pavel, C. Heuristic optimization of fluid temperature attenuator design with phase change material. In Proceedings of the International Conference on Soft Computing MENDEL, Brno, Czech Republic, 10–12 July 2012; pp. 338–343. [Google Scholar]
  21. Mohebbi, R.; Rashidi, M.M. Numerical simulation of natural convection heat transfer of a nanofluid in an l-shaped enclosure with a heating obstacle. J. Taiwan Inst. Chem. Eng. 2017, 72, 70–84. [Google Scholar] [CrossRef]
  22. Sarafraz, M.M.; Safaei, M.R. Diurnal thermal evaluation of an evacuated tube solar collector (etsc) charged with graphene nanoplatelets-methanol nano-suspension. Renew. Energy 2019, 142, 364–372. [Google Scholar] [CrossRef]
Figure 1. Schematic diagram of the enhanced circulating cooling water (CCW) system with the dynamic thermal filtering method (DTFM) attenuator.
Figure 1. Schematic diagram of the enhanced circulating cooling water (CCW) system with the dynamic thermal filtering method (DTFM) attenuator.
Applsci 10 05338 g001
Figure 2. Axial and radial sectional views of tube-tank heat exchanger.
Figure 2. Axial and radial sectional views of tube-tank heat exchanger.
Applsci 10 05338 g002
Figure 3. Theoretical temperature fluctuation attenuation ratio of the proposed DTFM attenuator.
Figure 3. Theoretical temperature fluctuation attenuation ratio of the proposed DTFM attenuator.
Applsci 10 05338 g003
Figure 4. Schematic diagram of experimental setup.
Figure 4. Schematic diagram of experimental setup.
Applsci 10 05338 g004
Figure 5. Photo of experimental setup (First CCW flow loop: 1-3-6-4-1; Second CCW flow loop: 2-3-6-4-2. Signal loop: 7-5-3, 4).
Figure 5. Photo of experimental setup (First CCW flow loop: 1-3-6-4-1; Second CCW flow loop: 2-3-6-4-2. Signal loop: 7-5-3, 4).
Applsci 10 05338 g005
Figure 6. Temperature waveforms of CCW at inlet header and outer header of the DTFM attenuator.
Figure 6. Temperature waveforms of CCW at inlet header and outer header of the DTFM attenuator.
Applsci 10 05338 g006
Figure 7. Performance of temperature fluctuation attenuation in frequency domain.
Figure 7. Performance of temperature fluctuation attenuation in frequency domain.
Applsci 10 05338 g007
Figure 8. Experimental results of temperature fluctuation attenuation ratio (Compared with theoretical results in Figure 3).
Figure 8. Experimental results of temperature fluctuation attenuation ratio (Compared with theoretical results in Figure 3).
Applsci 10 05338 g008

Share and Cite

MDPI and ACS Style

Lu, Y.; Cui, J.; Tan, J.; Bian, X.; Zhao, Y. Temperature Fluctuation Attenuation of Circulating Cooling Water Using Dynamic Thermal Filtering. Appl. Sci. 2020, 10, 5338. https://doi.org/10.3390/app10155338

AMA Style

Lu Y, Cui J, Tan J, Bian X, Zhao Y. Temperature Fluctuation Attenuation of Circulating Cooling Water Using Dynamic Thermal Filtering. Applied Sciences. 2020; 10(15):5338. https://doi.org/10.3390/app10155338

Chicago/Turabian Style

Lu, Yesheng, Junning Cui, Jiubin Tan, Xingyuan Bian, and Yamin Zhao. 2020. "Temperature Fluctuation Attenuation of Circulating Cooling Water Using Dynamic Thermal Filtering" Applied Sciences 10, no. 15: 5338. https://doi.org/10.3390/app10155338

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.