Ventilation Induced in an Isolated Subsurface Structure by Natural Forces: Method Development and Application

Thomas Neil McManus and Assed Haddad    

Resumen

It is believed that isolated subsurface structures of an infrastructure do not ventilate through opening(s) in manhole covers. The literature has almost no information on this topic. This study reports on considerations involved in the development and utilization of a method to study this question. Carbon monoxide (CO) is readily obtainable in engine exhaust, easily detectable at very low concentration, and is relatively safe to handle, which makes it ideal for use as a tracer gas. Transfer into the airspace of the structure was carried out using metal tubing. This study examined the engine operating time and the number of openings in a manhole cover. CO was measured using four instruments in the vertical profile. It was found to generally decrease in a narrow band, initially linearly through a curvilinear region and a linear tail. Clearance of most of the contaminant occurred rapidly during the first part of the process. A decrease to 25 ppm required from 439 min (7 openings) to 1118 min (1 opening). Ambient temperature and near-surface air flow likely influenced these values. The measurement profiles strongly suggest that the atmosphere in the airspace was rapidly and thoroughly well-mixed. The methodology developed and reported here is suitable for a more expanded investigation, the intent being to identify modifications of the design to optimize the process.

 Artículos similares

       
 
Thomas Neil McManus and Assed Haddad    
Isolated subsurface structures readily collect solvents spilled onto surrounding surfaces or poured into opening(s) in the manhole cover. Fatal overexposures and fires/explosions have occurred following these events. This work documents evaporation of 10... ver más
Revista: Infrastructures

 
This study reports on near-surface airspeed measured using a fast-responding thermoanemometer during an investigation of ventilation of an isolated subsurface structure induced by natural forces. Air speed changes continuously, rapidly, and unpredictably... ver más
Revista: Infrastructures

 
Travis A. Smith, Jason K. Jolliff, Nan D. Walker and Stephanie Anderson    
Tropical cyclone induced phytoplankton productivity is examined using a tropical cyclone version of the Coupled Ocean/Atmosphere Mesoscale Prediction System (COAMPS®). A four-component Nutrient?Phytoplankton?Detritus biological model is integrated into C... ver más

 
Lu Aye, Robert Fuller     Pág. 32 - 39
Melbourne's climatic conditions demand that its buildings require both heating and cooling systems. In a multi-storey office building , however, cooling requirements will dominate. How the internal space is cooled and ventilation air is delivered will si... ver más

 